- 256×96像素图形显示器,带有白色LED背光。
- 菜单操作简易,电阻式触屏界面。
- 通过ModBus RS485或Sub1Ghz无线电 (868MHz)向数据管理器发送数据。
- 连接单台EW 900数据管理器的最大距离为250米。
- 三相/单相电源表。
- 有功能量、无功能量和视在能量监测。
- 有功功率、无功功率和视在功率监测。
- 电气参数测量:电流,电压,有功功率、无功功率与视在功率,功率因数。
- 电网质量测量:谐波(1至51),总谐波失真。
- 精度:有功能量1级。
- 更新数据:1秒。
EW800A
DEM(Distributed Embedded Meter,分布式嵌入式仪表),内置电流测量分流器,可测电流高达64A,内置可触摸式LCD显示器
- 内置I/O模块,2路数字输入和2路数字输出
- RS485串口通讯接口
- RF868MHz无线通讯接口
EW800A DEM | |
---|---|
Connections | Single-phase Three-phase 4 wires with Y load Three-phase 4 wires with D load |
Measuring inputs - Current Channels | Direct up to 64A (45kW) three-phase connection, up to 21A (15kW) single-phase connection |
Measuring inputs - Voltage Channels | Direct (max rated voltage phase-neutral 230Vac) |
Power supply | self-powered |
Communication | RS485 ModBus (in all EW800… models) Radio RF868 MHz (only in EW800…200 models) Ethernet (only in EW800…300 models) |
Digital Isolated Input/Output | 2 I/O module option (configurable by Data Manager) THD |
Measures | Voltage (phase-neutral and phase-phase) Current (phase values and neutral value) Imported Active Energy (phase values and total value) Exported Active Energy (phase values and total value) Imported Active Power (phase values and total value) Exported Active Power (phase values and total value) Reactive Power with sign (phase values and total value) Apparent Power (phase values and total value) Power Factor (phase values and total value) Frequency |
Harmonic analysis | THD (in voltage / current signal) Harmonics 1st ...51st (in voltage / current signal) |
Accuracy - Active Energy (according to IED 62053-21) | Class 1 |
Accuracy - Reactive Energy (according to IED 62053-23) | Class 2 |
Accuracy - Current and Voltage | ≤ 0,5% |
Display | LCD (256 x 96 pixel) and resistive touch screen |
Case - Mounting | DIN rail |
Case - No. DIN modules | 7 |
Case - External dimensions (mm) | 126 x 100 x 70 |
EW800B
DTM(Distributed External CTs Meter,分布式外接CTs仪表),配备测量电流的外接CTs,内置可触摸式LCD显示器
- 内置I/O模块,2路数字输入和2路数字输出
- RS485串口通讯接口
- RF868MHz无线通讯接口
EW800B DTM | |
---|---|
Connections | Single-phase Two-phase Three-phase with neutral Three-phase without neutral |
Measuring inputs - Current Channels | with external Current Transformers |
Measuring inputs - Voltage Channels | Direct (max rated voltage phase-neutral 230Vac) or with external Voltage Transformer (rated secondary voltage 100-115Vac, for LV or MV application) |
Power supply | 100÷230Vac |
Communication | RS485 ModBus (in all EW800… models) Radio RF868 MHz (only in EW800…200 models) Ethernet (only in EW800…300 models) |
Digital Isolated Input/Output | Voltage (phase-neutral and phase-phase) Current (phase values and neutral value) Imported Active Energy (phase values and total value) Exported Active Energy (phase values and total value) Imported Active Power (phase values and total value) Exported Active Power (phase values and total value) Reactive Power with sign (phase values and total value) Apparent Power (phase values and total value) Power Factor (phase values and total value) Frequency |
Harmonic analysis | THD (in voltage / current signal) Harmonics 1st ...51st (in voltage / current signal) |
Accuracy - Active Energy (according to IED 62053-21) | Class 1 |
Accuracy - Reactive Energy (according to IED 62053-23) | Class 2 |
Accuracy - Current and Voltage | ≤ 0,5% |
Display | LCD (256 x 96 pixel) and resistive touch screen |
Case - Mounting | DIN rail |
Case - No. DIN modules | 5 |
Case - External dimensions (mm) | 90 x 96 x 70 |
EW800C
DRM (Distributed External Rogowski Meter,分布式外接Rogowski仪表),配备测量电流的外接Rogowski,内置可触摸式LCD显示器
- 内置I/O模块,2路数字输入和2路数字输出
- RS485串口通讯接口
- RF868MHz无线通讯接口
EW800C DRM | |
---|---|
Connections | Single-phase Two-phase Three-phase with neutral Three-phase without neutral |
Measuring inputs - Current Channels | with external Rogowski coils |
Measuring inputs - Voltage Channels | Direct (max rated voltage phase-neutral 230Vac) or with external Voltage Transformer (rated secondary voltage 100-115Vac, for LV or MV application) |
Power supply | 100÷230Vac |
Communication | RS485 ModBus (in all EW800… models) Radio RF868 MHz (only in EW800…200 models) Ethernet (only in EW800…300 models) |
Digital Isolated Input/Output | 2 I/O module option (configurable by Data Manager) |
Measures | Voltage (phase-neutral and phase-phase) Current (phase values and neutral value) Imported Active Energy (phase values and total value) Exported Active Energy (phase values and total value) Imported Active Power (phase values and total value) Exported Active Power (phase values and total value) Reactive Power with sign (phase values and total value) Apparent Power (phase values and total value) Power Factor (phase values and total value) Frequency |
Harmonic analysis | THD (in voltage / current signal) Harmonics 1st ...51st (in voltage / current signal) |
Accuracy - Active Energy (according to IED 62053-21) | Class 1 |
Accuracy - Reactive Energy (according to IED 62053-23) | Class 2 |
Accuracy - Current and Voltage | ≤ 0,5% |
Display | LCD (256 x 96 pixel) and resistive touch screen |
Casec -Mounting | DIN rail |
Case - No. DIN modules | 5 |
Case - External dimensions (mm) | 90 x 96 x 70 |
代码
CODES | DESCRIPTION |
---|---|
EW800A | |
EW800A3A100 | DEM (Distributed Embedded Meter) with internal shunts for current measurements up to 64A - integrated touch LCD display - serial communication interface RS485 |
EW800A3A122 | DEM (Distributed Embedded Meter) with internal shunts for current measurements up to 64A - integrated I/O module with 2 digital inputs and 2 digital outputs - integrated touch LCD display - serial communication interface RS485 |
EW800A3A200 | DEM (Distributed Embedded Meter) with internal shunts for current measurements up to 64A - integrated touch LCD display - radio communication interface RF868 MHZ |
EW800A3A222 | DEM (Distributed Embedded Meter) with internal shunts for current measurements up to 64A - integrated I/O module with 2 digital inputs and 2 digital outputs - integrated touch LCD display - radio communication interface RF868 MHZ |
EW800B | |
EW800B3A100 | DTM (Network External TA Meter) with external TA for current measurements - integrated touch LCD display - serial communication interface RS485 |
EW800B3A122 | DTM (Distributed External TA Meter) with external TA for current measurements - integrated I/O module with 2 digital inputs and 2 digital outputs - integrated touch LCD display - serial communication interface RS485 |
EW800B3A200 | DTM (Distributed External TA Meter) with external TA for current measurements - integrated touch LCD display - radio communication interface RF868 MHZ |
EW800B3A222 | DTM (Distributed External TA Meter) with external TA for current measurements - integrated I/O module with 2 digital inputs and 2 digital outputs - integrated touch LCD display - radio communication interface RF868 MHZ |
EW800B3A300 | DTM (Distributed External TA Meter) with external TA for current measurements - integrated touch LCD display - Modbus TCP/IP LAN interface |
EW800B3A322 | DTM (Distributed External TA Meter) with external TA for current measurements - integrated I/O module with 2 digital inputs and 2 digital outputs - integrated touch LCD display - Modbus TCP/IP LAN interface |
EW800C | |
EW800C3A100 | DRM (Distributed External Rogowski Meter) with external Rogowski coils for current measurements - integrated touch LCD display - serial communication interface RS485 |
EW800C3A122 | DRM (Distributed External Rogowski Meter) with external Rogowski coils for current measurements - integrated I/O module with 2 digital inputs and 2 digital outputs - integrated touch LCD display - serial communication interface RS485 |
EW800C3A200 | DRM (Distributed External Rogowski Meter) with external Rogowski coils for current measurements - integrated touch LCD display - radio communication interface RF868 MHZ |
EW800C3A222 | DRM (Distributed External Rogowski Meter) with external Rogowski coils for current measurements - integrated I/O module with 2 digital inputs and 2 digital outputs - integrated touch LCD display - radio communication interface RF868 MHZ |
EW800C3A300 | DRM (Distributed External Rogowski Meter) with external Rogowski coils for current measurements - integrated touch LCD display - Modbus TCP/IP LAN interface |
EW800C3A322 | DRM (Distributed External Rogowski Meter) with external Rogowski coils for current measurements - integrated I/O module with 2 digital inputs and 2 digital outputs - integrated touch LCD display - Modbus TCP/IP LAN interface |